Cookies på Omegas websteder Vi anvender cookies på vores websted. Disse cookies er afgørende for, at webstedet kan fungere korrekt. Hvis du fortsætter uden at ændre dine indstillinger, antager vi, at du gerne vil modtage alle de cookies, der anvendes på dette websted. Du finder flere oplysninger om cookies ved at klikke her
Differential Pressure Transmitter with two accuracy versions, for dry clean gases.
SPECIFICATIONS Excitation: 12 to 36 Vdc Output: 4 to 20 mA (2 wire) Operating Temp: -29 to 85°C (-20 to 185°F) Compensated Temp: -18 to 72°C (0 to 160°F) Thermal Effects: Zero: 0.015% FS/°F Span: 0.015% FS/°F Proof Pressure: 10 psi Burst Pressure: 50 psi Static Pressure: 100 psi Sensor Type: Capacitance Max Loop Resistance: (Supply voltage - 12) x 50 Ω Calibration Report: NIST calibration at 25, 50, 75 and 100% FS; upscale and downscale provided Response Time: 250 ms Wetted Parts: Dry, clean non-corrosive gases only Enclosure: NEMA 4X (IP65); 137 L x 76 W x 64 mm D (5.4 x 3 x 2.5") Pressure Port: ¼ NPTF Electrical Conn: Screw terminal (two ½ NPTF conduit) Weight: 955 g (2.1 lb)
† All amounts shown in EUR Noter: Comes with complete operator’s manual. To Order the High Accuracy PX657, (0.15%). See Part Number Builder below.
Delnummerberegner
Build Your Part Number Below
Beskrivelse af tilvalg:
(1)
Accuracy select from: 6 for Standard Accuracy 7 for High Accuracy
(2)
Range (inH2O) select from: 0.1 for 0-0.1 0.25 for 0-0.25 0.5 for 0-0.5 01 for 0-1 02 for 0-2 03 for 0-3 05 for 0-5 10 for 0-10 25 for 0-25 50 for 0-50 100 for 0-100 200 for 0-200 0.05B for ± 0.05 0.25B for ± 0.25 0.50B for ± 0.50 01B for ± 1 2.5B for ± 2.5 05B for ± 5 10B for ± 10 25B for ± 25 50B for ± 50 100B for ± 100
Noter: Ikke alle kombinationer er nødvendigvis gyldige. Se specifikationerne for gyldige delnumre.